WaterToAirHeatPump statics fix #8665

Merged
merged 1 commit into from
Mar 27, 2021
Merged

WaterToAirHeatPump statics fix #8665

merged 1 commit into from
Mar 27, 2021

Conversation

mitchute
Copy link
Collaborator

@mitchute mitchute commented Mar 27, 2021

Pull request overview

Pull Request Author

Add to this list or remove from it as applicable. This is a simple templated set of guidelines.

  • Title of PR should be user-synopsis style (clearly understandable in a standalone changelog context)
  • Label the PR with at least one of: Defect, Refactoring, NewFeature, Performance, and/or DoNoPublish
  • Pull requests that impact EnergyPlus code must also include unit tests to cover enhancement or defect repair
  • Author should provide a "walkthrough" of relevant code changes using a GitHub code review comment process
  • If any diffs are expected, author must demonstrate they are justified using plots and descriptions
  • If changes fix a defect, the fix should be demonstrated in plots and descriptions
  • If any defect files are updated to a more recent version, upload new versions here or on DevSupport
  • If IDD requires transition, transition source, rules, ExpandObjects, and IDFs must be updated, and add IDDChange label
  • If structural output changes, add to output rules file and add OutputChange label
  • If adding/removing any LaTeX docs or figures, update that document's CMakeLists file dependencies

Reviewer

This will not be exhaustively relevant to every PR.

  • Perform a Code Review on GitHub
  • If branch is behind develop, merge develop and build locally to check for side effects of the merge
  • If defect, verify by running develop branch and reproducing defect, then running PR and reproducing fix
  • If feature, test running new feature, try creative ways to break it
  • CI status: all green or justified
  • Check that performance is not impacted (CI Linux results include performance check)
  • Run Unit Test(s) locally
  • Check any new function arguments for performance impacts
  • Verify IDF naming conventions and styles, memos and notes and defaults
  • If new idf included, locally check the err file and other outputs

@mitchute mitchute added Defect Includes code to repair a defect in EnergyPlus DoNotPublish Includes changes that shouldn't be reported in the changelog labels Mar 27, 2021
@mitchute mitchute added this to the EnergyPlus 9.5.0 milestone Mar 27, 2021
@mitchute mitchute self-assigned this Mar 27, 2021
@mitchute mitchute marked this pull request as draft March 27, 2021 01:11
@mitchute
Copy link
Collaborator Author

@mjwitte maybe there's another issue here. After correcting the static issue you referenced, still I'm not able to get E+ to even run to that point. Err file posted below for reference.

Program Version,EnergyPlus, Version 9.5.0-f56b20e6b1, YMD=2021.03.26 19:06,
   ** Warning ** Timestep: Requested number (1) is less than the suggested minimum of 4.
   **   ~~~   ** Please see entry for Timestep in Input/Output Reference for discussion of considerations.
   ** Warning ** ProcessScheduleInput: Schedule:Constant="ALWAYS ON CONTINUOUS", Blank schedule_type_limits_name input -- will not be validated.
   ** Warning ** Weather file location will be used rather than entered (IDF) Location object.
   **   ~~~   ** ..Location object=DENVER INTL AP_CO_USA
   **   ~~~   ** ..Weather File Location=Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
   **   ~~~   ** ..due to location differences, Latitude difference=[2.15] degrees, Longitude difference=[16.73] degrees.
   **   ~~~   ** ..Time Zone difference=[1.0] hour(s), Elevation difference=[87.82] percent, [1449.00] meters.
   ** Severe  ** GetProjectControlData: Building: loads_convergence_tolerance_value value invalid, [0.000]
   ** Severe  ** GetProjectControlData: Building: loads_convergence_tolerance_value value invalid, [0.000]
   ** Severe  ** GetProjectControlData: Building: solar_distribution invalid=
   ** Warning ** Shading:Building:Detailed="WINDOWNORTH SHADING SURFACE", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** Shading:Building:Detailed="WINDOWSOUTH SHADING SURFACE", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** Shading:Building:Detailed="WINDOWWEST SHADING SURFACE", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="CEILINGOTHER", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="FLOOROTHER", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="WALL:0", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="WALL:90", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="WALL:180", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="WALL:270", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="WALLOTHER", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="SURFACE DOOR", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="SURFACE WINDOWNORTH", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="SURFACE WINDOWSOUTH", number_of_vertices not even multiple of 3. Will read in 3
   ** Warning ** BuildingSurface:Detailed="SURFACE WINDOWWEST", number_of_vertices not even multiple of 3. Will read in 3
   ** Severe  ** GetHTSubSurfaceData: Surface Openings have too much area for base surface=SURFACE DOOR
   **   ~~~   ** Opening Surface creating error=DOOR
   ** Severe  ** GetHTSubSurfaceData: Surface Openings have too much area for base surface=SURFACE WINDOWNORTH
   **   ~~~   ** Opening Surface creating error=WINDOWNORTH
   ** Severe  ** GetHTSubSurfaceData: Surface Openings have too much area for base surface=SURFACE WINDOWSOUTH
   **   ~~~   ** Opening Surface creating error=WINDOWSOUTH
   ** Severe  ** GetHTSubSurfaceData: Surface Openings have too much area for base surface=SURFACE WINDOWWEST
   **   ~~~   ** Opening Surface creating error=WINDOWWEST
   **  Fatal  ** GetSurfaceData: Errors discovered, program terminates.
   ...Summary of Errors that led to program termination:
   ..... Reference severe error count=7
   ..... Last severe error=GetHTSubSurfaceData: Surface Openings have too much area for base surface=SURFACE WINDOWWEST
   ************* Warning:  Node connection errors not checked - most system input has not been read (see previous warning).
   ************* Fatal error -- final processing.  Program exited before simulations began.  See previous error messages.
   ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Sizing Error Summary. During Sizing: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Terminated--Fatal Error Detected. 17 Warning; 7 Severe Errors; Elapsed Time=00hr 00min  3.26sec

@mjwitte
Copy link
Contributor

mjwitte commented Mar 27, 2021

@mitchute Sorry., This file needs the fixes in #8661 to get past the input errors. I can try to make one that runs with develop but still trips over the initialization problem.

@mitchute
Copy link
Collaborator Author

OK, thanks @mjwitte. It does run on through after merging your changes into this locally. I'm not sure if some of these warnings are relevant to your work, so I'm posting the error file here. Feel free to merge this if you're OK with the changes.

Program Version,EnergyPlus, Version 9.5.0-f56b20e6b1, YMD=2021.03.27 06:39,
   ** Warning ** Timestep: Requested number (1) is less than the suggested minimum of 4.
   **   ~~~   ** Please see entry for Timestep in Input/Output Reference for discussion of considerations.
   ** Warning ** ProcessScheduleInput: Schedule:Constant="ALWAYS ON CONTINUOUS", Blank schedule_type_limits_name input -- will not be validated.
   ** Warning ** Weather file location will be used rather than entered (IDF) Location object.
   **   ~~~   ** ..Location object=DENVER INTL AP_CO_USA
   **   ~~~   ** ..Weather File Location=Chicago Ohare Intl Ap IL USA TMY3 WMO#=725300
   **   ~~~   ** ..due to location differences, Latitude difference=[2.15] degrees, Longitude difference=[16.73] degrees.
   **   ~~~   ** ..Time Zone difference=[1.0] hour(s), Elevation difference=[87.82] percent, [1449.00] meters.
   ** Warning ** CalculateZoneVolume: 1 zone is not fully enclosed. For more details use:  Output:Diagnostics,DisplayExtrawarnings; 
   ** Warning ** CheckUsedConstructions: There are 1 nominally unused constructions in input.
   **   ~~~   ** For explicit details on each unused construction, use Output:Diagnostics,DisplayExtraWarnings;
   ** Warning ** Check input. Pump nominal power or motor efficiency is set to 0, for pump=PUMP VARIABLE SPEED 1
   ** Warning ** Output:Meter: invalid key_name="ELECTRICITYPRODUCED:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="NATURALGAS:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="FUELOILNO2:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="PROPANE:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="OTHERFUEL1:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="OTHERFUEL2:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="COAL:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="GARAGE LIGHTING:INTERIORLIGHTS:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="FREEZER:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="CEILING FAN:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC ELECTRIC VEHICLE CHARGING:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC WELL PUMP:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC POOL HEATER:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC POOL PUMP:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC HOT TUB HEATER:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC HOT TUB PUMP:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="PHOTOVOLTAIC:ELECTRICITYPRODUCED" - not found.
   ** Warning ** Output:Meter: invalid key_name="POWERCONVERSION:ELECTRICITYPRODUCED" - not found.
   ** Warning ** Output:Meter: invalid key_name="COGENERATION:ELECTRICITYPRODUCED" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC POOL HEATER:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC HOT TUB HEATER:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="COGENERATION:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="COGENERATION:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="NATURALGAS:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="FUELOILNO2:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="PROPANE:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="OTHERFUEL1:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="OTHERFUEL2:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="COAL:FACILITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="GARAGE LIGHTING:INTERIORLIGHTS:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="FREEZER:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="CEILING FAN:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC ELECTRIC VEHICLE CHARGING:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC WELL PUMP:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC POOL HEATER:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC POOL PUMP:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC HOT TUB HEATER:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC HOT TUB PUMP:INTERIOREQUIPMENT:ELECTRICITY" - not found.
   ** Warning ** Output:Meter: invalid key_name="PHOTOVOLTAIC:ELECTRICITYPRODUCED" - not found.
   ** Warning ** Output:Meter: invalid key_name="POWERCONVERSION:ELECTRICITYPRODUCED" - not found.
   ** Warning ** Output:Meter: invalid key_name="COGENERATION:ELECTRICITYPRODUCED" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC POOL HEATER:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC HOT TUB HEATER:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="COGENERATION:NATURALGAS" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:FUELOILNO2" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="COGENERATION:PROPANE" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:OTHERFUEL1" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:OTHERFUEL2" - not found.
   ** Warning ** Output:Meter: invalid key_name="CLOTHES DRYER:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="COOKING RANGE:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC GRILL:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC LIGHTING:INTERIOREQUIPMENT:COAL" - not found.
   ** Warning ** Output:Meter: invalid key_name="MISC FIREPLACE:INTERIOREQUIPMENT:COAL" - not found.
   ************* Testing Individual Branch Integrity
   ************* All Branches passed integrity testing
   ************* Testing Individual Supply Air Path Integrity
   ************* All Supply Air Paths passed integrity testing
   ************* Testing Individual Return Air Path Integrity
   ************* All Return Air Paths passed integrity testing
   ************* No node connection errors were found.
   ************* Beginning Simulation
   ** Warning ** GetSpecificHeatGlycol: Temperature is out of range (too low) for fluid [WATER] specific heat supplied values **
   **   ~~~   ** ..Called From:PlantLoopSolver::UpdateAnyLoopDemandAlterations,Temperature=[-1.95], supplied data range=[0.00,125.00]
   **   ~~~   **  Environment=RUN PERIOD 1, at Simulation time=01/05 07:00 - 08:00
   ** Warning ** GetDensityGlycol: Temperature is out of range (too low) for fluid [WATER] density **
   **   ~~~   ** ..Called From:NodeReportingCalc:NODE 9,Temperature=[-1.95], supplied data range=[0.00,100.00]
   **   ~~~   **  Environment=RUN PERIOD 1, at Simulation time=01/05 07:00 - 08:00
   ************* Simulation Error Summary *************
   ** Warning ** The following Report Variables were requested but not generated -- check.rdd file
   **   ~~~   ** Either the IDF did not contain these elements, the variable name is misspelled,
   **   ~~~   ** or the requested variable is an advanced output which requires Output : Diagnostics, DisplayAdvancedReportVariables;
   ************* Key=ideal, VarName=ZONE IDEAL LOADS ZONE SENSIBLE HEATING ENERGY, Frequency=
   ************* Key=ideal, VarName=ZONE IDEAL LOADS ZONE SENSIBLE COOLING ENERGY, Frequency=
   ************* Key=ground source heat pump clg coil, VarName=COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER ELECTRICITY ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST ELECTRICITY ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL COAL ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER COAL ENERGY, Frequency=
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST COAL ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER ELECTRICITY ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST ELECTRICITY ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL COAL ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER COAL ENERGY, Frequency=
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST COAL ENERGY, Frequency=
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY NATURALGAS ENERGY, Frequency=
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY FUELOILNO2 ENERGY, Frequency=
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY PROPANE ENERGY, Frequency=
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY OTHERFUEL1 ENERGY, Frequency=
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY OTHERFUEL2 ENERGY, Frequency=
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY COAL ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER NATURALGAS ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC NATURALGAS ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC NATURALGAS ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER FUELOILNO2 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC FUELOILNO2 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC FUELOILNO2 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER PROPANE ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC PROPANE ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC PROPANE ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OTHERFUEL1 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC OTHERFUEL1 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC OTHERFUEL1 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OTHERFUEL2 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC OTHERFUEL2 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC OTHERFUEL2 ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER COAL ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC COAL ENERGY, Frequency=
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC COAL ENERGY, Frequency=
   ************* Key=other heated space, VarName=SCHEDULE VALUE, Frequency=Monthly
   ************* Key=other multifamily buffer space, VarName=SCHEDULE VALUE, Frequency=Monthly
   ************* Key=other non-freezing space, VarName=SCHEDULE VALUE, Frequency=Monthly
   ************* Key=other housing unit, VarName=SCHEDULE VALUE, Frequency=Monthly
   ************* Key=exterior wall, VarName=SCHEDULE VALUE, Frequency=Monthly
   ************* Key=under slab, VarName=SCHEDULE VALUE, Frequency=Monthly
   ************* Key=ground source heat pump clg coil, VarName=COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER ELECTRICITY ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST ELECTRICITY ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL COAL ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL CRANKCASE HEATER COAL ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump htg coil, VarName=HEATING COIL DEFROST COAL ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER ELECTRICITY ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST ELECTRICITY ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL COAL ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL CRANKCASE HEATER COAL ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump backup htg coil, VarName=HEATING COIL DEFROST COAL ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY PROPANE ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=ground source heat pump unitary system, VarName=UNITARY SYSTEM HEATING ANCILLARY COAL ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC NATURALGAS ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC FUELOILNO2 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER PROPANE ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC PROPANE ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC PROPANE ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC OTHERFUEL1 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC OTHERFUEL2 ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER COAL ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER OFF CYCLE PARASITIC COAL ENERGY, Frequency=Monthly
   ************* Key=water heater, VarName=WATER HEATER ON CYCLE PARASITIC COAL ENERGY, Frequency=Monthly
   ************* There are 1 unused objects in input.
   ************* Use Output:Diagnostics,DisplayUnusedObjects; to see them.
   ************* There are 3 unused schedules in input.
   ************* There are 3 unused week schedules in input.
   ************* There are 5 unused day schedules in input.
   ************* Use Output:Diagnostics,DisplayUnusedSchedules; to see them.
   *************
   ************* ===== Recurring Error Summary =====
   ************* The following recurring error messages occurred.
   *************
   *************  ** Warning ** GetSpecificHeatGlycol: Temperature out of range (too low) for fluid [WATER] specific heat **
   *************  **   ~~~   **   This error occurred 4 total times;
   *************  **   ~~~   **   during Warmup 0 times;
   *************  **   ~~~   **   during Sizing 0 times.
   *************  **   ~~~   **   Max=-1.056213 {C}  Min=-1.954384 {C}
   *************
   *************  ** Warning ** GetDensityGlycol: Temperature out of range (too low) for fluid [WATER] density **
   *************  **   ~~~   **   This error occurred 12 total times;
   *************  **   ~~~   **   during Warmup 0 times;
   *************  **   ~~~   **   during Sizing 0 times.
   *************  **   ~~~   **   Max=-1.548848 {C}  Min=-1.954384 {C}
   *************
   *************
   ************* ===== Final Error Summary =====
   ************* The following error categories occurred.  Consider correcting or noting.
   ************* Nominally Unused Constructions
   ************* ..The nominally unused constructions warning is provided to alert you to potential conditions that can cause
   ************* ..extra time during simulation. Each construction is calculated by the algorithm indicated in the HeatBalanceAlgorithm
   ************* ..object. You may remove the constructions indicated (when you use the DisplayExtraWarnings option).
   *************
   ************* EnergyPlus Warmup Error Summary. During Warmup: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Sizing Error Summary. During Sizing: 0 Warning; 0 Severe Errors.
   ************* EnergyPlus Completed Successfully-- 128 Warning; 0 Severe Errors; Elapsed Time=00hr 00min 44.38sec

@mjwitte
Copy link
Contributor

mjwitte commented Mar 27, 2021

@mitchute Also, the idf version of that file will run to the failure point with plain develop.
GHX-idf-fix.idf.txt

@mjwitte mjwitte marked this pull request as ready for review March 27, 2021 14:08
Copy link
Contributor

@mjwitte mjwitte left a comment

Choose a reason for hiding this comment

The reason will be displayed to describe this comment to others. Learn more.

Tested the idf version of the defect file with develop and this branch. Problem solved. Thanks @mitchute

@mjwitte mjwitte merged commit ad764b9 into develop Mar 27, 2021
@mjwitte mjwitte deleted the wahp_static_fix branch March 27, 2021 14:17