Add BESTEST test acceptance criteria limits #3401
Conversation
Buildings/ThermalZones/Detailed/Validation/BESTEST/Data/CriteriaLimits.mo
Outdated
Show resolved
Hide resolved
Buildings/Resources/src/ThermalZones/Detailed/Validation/BESTEST/simulateAndPlot.py
Outdated
Show resolved
Hide resolved
Buildings/ThermalZones/Detailed/Validation/BESTEST/Data/CriteriaLimits.mo
Outdated
Show resolved
Hide resolved
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Please see the inline comments.
@mwetter Your comments have been addressed. |
@JayHuLBL : Would Case980 pass if the tolerance is increased, or the number of elements for the heat transfer discretization is increased? |
Since your last review, I changed the number of state as: The annual cooling load of Case980 ( |
@mwetter I changed the code and now there are other three tools ( I have also tested different PID control gains but the impacts are minor. I would suggest keeping the results as it is. |
* adding the limits to the userGuide * flagged all the results --------- Co-authored-by: Michael Wetter <mwetter@lbl.gov>
This closes #3396.
ASHRAE140_data.dat
fileCases6xx
andCases9xx